The HBP-111 occupancy sensor is designed for automatic lighting control in high or low bay applications. It contains a passive infrared (PIR) sensor and a lens engineered to provide reliable coverage from a wide range of mounting heights. Sensitivity and time delay adjustments are set using trimpots conveniently locate on the sensor and can also be adjusted remotely using a handheld configuration tool (FSIR-100). The HBP-111 includes a hold-off daylight light level feature to prevent  lighting from turning on wen occupancy is detected when there is sufficient ambient light available.

See Spec Sheet

    Specifications:

    • Relay load ratings:
      • 120VAC, 60Hz: 0-1000VA, 1/4hp
      • 230VAC, 50/60Hz: 0-1000VA
      • 277VAC, 60Hz: 0-1200VA, 1/4hp
      • 347VAC, 60Hz: 0-1500VA, 1/4hp
    • Compatible load types: Tungsten, electronic and magnetic ballasts, fluorescent and LED
    • Time delay (5, 10, 15, 20, 30 min. via trimpot; 1-30 min. via FSIR-100; default 15 min.)
    • Hold-off light level (1-300fc; default 300fc; disable hold-off light level via FSIR-100)
    • Sensitivity (max, med, low via trimpot or FSIR-100; default max)
    • Push button functions: manual mode, test mode, service mode, fail-on mode, fail-off mode, factory default, burn-in mode, walk-through mode, visual alert, service mode
    • Operating conditions: Temperature 32-158°F (0-70°C); Humidity 5-95%, non-condensing
    • Indoor use only
    • Materials: ABS, flame retardant, impact resistant

    Fixture Ordering Information

    PART #DESCRIPTION
    HBP111Wattstopper HBP-111 high/low bay PIR motion sensor with IR remote capabilities
    FSIR100Wattstopper FSIR-100 wireless configuration tool for FSP-211/HBP-111